Biogenic sulfide corrosion

Biogenic sulfide corrosion is a bacterially mediated process of forming hydrogen sulfide gas and the subsequent conversion to sulfuric acid that attacks concrete and steel within wastewater environments. The hydrogen sulfide gas is biochemically oxidized in the presence of moisture to form sulfuric acid. The effect of sulfuric acid on concrete and steel surfaces exposed to severe wastewater environments can be devastating.[1] In the USA alone, corrosion is causing sewer asset losses estimated at around $14 billion per year.[2] This cost is expected to increase as the aging infrastructure continues to fail.[3]

Environment

Corrosion may occur where stale sewage generates hydrogen sulfide gas into an atmosphere containing oxygen gas and high relative humidity. There must be an underlying anaerobic aquatic habitat containing sulfates and an overlying aerobic aquatic habitat separated by a gas phase containing both oxygen and hydrogen sulfide at concentrations in excess of 2 ppm.[4]

Conversion of sulfate SO42− to hydrogen sulfide H2S

Fresh domestic sewage entering a wastewater collection system contains proteins including organic sulfur compounds oxidizable to sulfates and may contain inorganic sulfates.[5] Dissolved oxygen is depleted as bacteria begin to catabolize organic material in sewage. In the absence of dissolved oxygen and nitrates, sulfates are reduced to hydrogen sulfide as an alternative source of oxygen for catabolizing organic waste by sulfate reducing bacteria (SRB), identified primarily from the obligate anaerobic species Desulfovibrio.[4]

Hydrogen sulfide production depends on various physicochemical, topographic and hydraulic parameters[6] such as:

Conversion of hydrogen sulfide to sulfuric acid H2SO4

Some hydrogen sulfide gas diffuses into the headspace environment above the wastewater. Moisture evaporated from warm sewage may condense on unsubmerged walls of sewers, and is likely to hang in partially formed droplets from the horizontal crown of the sewer. As a portion of the hydrogen sulfide gas and oxygen gas from the air above the sewage dissolves into these stationary droplets, they become a habitat for sulfur oxidizing bacteria (SOB), of the genus Acidithiobacillus. Colonies of these aerobic bacteria metabolize the hydrogen sulfide gas to sulfuric acid.[4]

Corrosion

See also: Sulfidation

Sulfuric acid produced by microorganisms will interact with the surface of the structure material. For ordinary Portland cement, it reacts with the calcium hydroxide in concrete to form calcium sulfate. This change simultaneously destroys the polymeric nature of calcium hydroxide and substitutes a larger molecule into the matrix causing pressure and spalling of the adjacent concrete and aggregate particles.[7] The weakened crown may then collapse under heavy overburden loads.[8] Even within a well-designed sewer network, a rule of thumb in the industry suggests that 5% of the total length may/will suffer from biogenic corrosion. In these specific areas, biogenic sulfide corrosion can deteriorate metal or several millimeters per year of concrete (see Table).

Source Thickness loss

(in mm.y−1)

Material type
US EPA, 1991[9] 2.5 – 10 Concrete
Morton et al., 1991[10] 2.7 Concrete
Mori et al., 1992[11] 4.3 – 4.7 Concrete
Ismail et al., 1993[12] 2 – 4 Mortar
Davis, 1998[13] 3.1 Concrete
Monteny et al., 2001[14] 1.0 – 1.3 Mortar
Vincke et al., 2002[15] 1.1 – 1.8 Concrete

For calcium aluminate cements, processes are completely different because they are based on another chemical composition. At least three different mechanisms contribute to the better resistance to biogenic corrosion:[16]

A mortar made of calcium aluminate cement combined with calcium aluminate aggregates, i.e. a 100% calcium aluminate material, will last much longer as aggregates can also limit microorganisms’ growth and inhibits the acid generation at the source itself.

Prevention

There are several options to address biogenic sulfide corrosion problems: impairing H2S formation, venting out the H2S or using materials resistant to biogenic corrosion. For example, sewage flows more rapidly through steeper gradient sewers reducing time available for hydrogen sulfide generation. Likewise, removing sludge and sediments from the bottom of the pipes reduces the amount of anoxic areas responsible for sulfate reducing bacteria growth. Providing good ventilation of sewers can reduce atmospheric concentrations of hydrogen sulfide gas and may dry exposed sewer crowns, but this may create odor issues with neighbors around the venting shafts. Three other efficient methods can be used involving continuous operation of mechanical equipment: chemical reactant like calcium nitrate can be continuously added in the sewerage water to impair the H2S formation, an active ventilation through odor treatment units to remove H2S, or an injection of compressed air in pressurized mains to avoid the anaerobic condition to develop. In sewerage areas where biogenic sulfide corrosion is expected, acid resistant materials like calcium aluminate cements, PVC or vitrified clay pipe may be substituted to ordinary concrete or steel sewers.

See also

References

Notes

  1. O’Dea, Vaughn, “Understanding Biogenic Sulfide Corrosion,”MP (November 2007), pp. 36-39.
  2. Brongers et al., 2002
  3. Sydney et al., 1996; US EPA, 1991
  4. 1 2 3 Sawyer&McCarty p.461&462
  5. Metcalf & Eddy p.259
  6. US EPA, 1985
  7. USDI pp.9&10
  8. Hammer p.58
  9. United States Environmental Protection Agency, 1991. Hydrogen Sulphide Corrosion in Wastewater Collection and Treatment Systems (Technical Report)
  10. Morton R.L., Yanko W.A., Grahom D.W., Arnold R.G. (1991) Relationship between metal concentrations and crown corrosion in Los Angeles County sewers. Research Journal of Water Pollution Control Federation, 63, 789–798.
  11. Mori T., Nonaka T., Tazaki K., Koga M., Hikosaka Y., Noda S. (1992) Interactions of nutrients, moisture, and pH on microbial corrosion of concrete sewer pipes. Water Research, 26, 29–37.
  12. Ismail N., Nonaka T., Noda S., Mori T. (1993) Effect of carbonation on microbial corrosion of concrete. Journal of Construction Management and Engineering, 20, 133-138.
  13. Davis J.L. (1998) Characterization and modeling of microbially induced corrosion of concrete sewer pipes. Ph.D. Dissertation, University of Houston, Houston, TX.
  14. Monteny J., De Belie N., Vincke E., Verstraete W., Taerwe L. (2001) Chemical and microbiological tests to simulate sulfuric acid corrosion of polymer-modified concrete. Cement and Concrete Research, 31, 1359-1365.
  15. Vincke E., Van Wanseele E., Monteny J., Beeldens A., De Belie N., Taerwe L., Van Gemert D., Verstraete W. (2002) Influence of polymer addition on biogenic sulfuric acid attack. International Biodeterioration and Biodegradation, 49, 283-292.
  16. Herisson J., Van Hullebusch E., Gueguen Minerbe M., Chaussadent T. (2014) Biogenic corrosion mechanism: study of parameters explaining calcium aluminate cement durability. CAC 2014 – International Conference on Calcium Aluminates, May 2014, France. 12 p.

Pomeroy's report contains errors in the equation: the pipeline slope (S, p. 8) is quoted as m/100m, but should be m/m. This introduces a factor of 10 underestimate in the calculation of the 'Z factor', used to indicate if there is a risk of sulphide-induced corrosion, if the published units are used. The web link is to the revised 1992 edition, which contains the units error - the 1976 edition has the correct units.

This article is issued from Wikipedia - version of the Wednesday, March 23, 2016. The text is available under the Creative Commons Attribution/Share Alike but additional terms may apply for the media files.