Bootleg ground

In building wiring, a bootleg ground is an electrical ground that is wired from the neutral side of a receptacle or light fixture in an older 2-wire home.[1] This essentially connects the neutral side of the receptacle to the casing of an appliance or lamp. It can be a hazard because the neutral wire is a current-carrying conductor. In addition, a fault condition to a bootleg ground will not trip a GFCI breaker or a receptacle that is wired from the load side of a GFCI receptacle. Bootleg grounding is illegal and against code in many places. A safer alternative [NEC® Sec. 406.4(D)(2)(b)] if a grounding connection is not practicable (where a local electrical code allows it) is to install a GFCI and leave the grounding terminal screw unconnected, then place a label that says "No Equipment Ground" on the GFCI and a marking that states “GFCI Protected” and “No Equipment Ground” on all downstream receptacles.

120/240 volt circuits

Before 1996, in the United States it was common to ground the frames of 120/240-volt appliances (such as a clothes dryer or oven) to neutral (grounded conductors. This has been prohibited in new installations since the 1996 National Electrical Code® upon local adoption by legislation or regulation. Existing installations are permitted to continue in accordance with NEC® 250.140 Exception.

References

  1. Steven Bliss Troubleshooting Guide to Residential Construction Craftsman Book Company, 1997 ISBN 1-928580-23-8, page 287


This article is issued from Wikipedia - version of the Thursday, April 28, 2016. The text is available under the Creative Commons Attribution/Share Alike but additional terms may apply for the media files.