Cable fault location

Cable fault location is the process of locating periodic faults, such as insulation faults in underground cables, and is an application of electrical measurement systems. In this process, mobile shock discharge generators are among the devices used.

Early fault location device


Cable faults

Example of a cable fault

Cable faults are damage to cables which effect a resistance in the cable. If allowed to persist, this can lead to a voltage breakdown. There are different types of cable faults, which must first be classified before they can be located. The insulation of the cable plays a significant role in this. While paper-impregnated cables are particularly susceptible to external chemical and thermal influences, in high-voltage PE or XLPE cables the polyethylene insulation of the conductor is affected, leading to partial breakdowns and cracks that “eat away” the insulation.

Screening faults

A contact between conductor and screen generates a varying resistance.

Phase faults

The contact between multiple conductors generates a varying resistance.

Sheath faults

Sheath faults are damage of the cable sheath that allows the surroundings contact with the cable screen.

Faults due to moisture

Water penetrates into the cable sheath and contacts the conductors. Impedance changes at the fault location make measuring more difficult. The resistance usually lies in the low-ohmic range.

Disruptions

Combination of series and parallel resistances, usually in the form of a wire break. The voltage is interrupted, i.e. Ω=∞ .

Cable testing

To locate a fault in the cable, the cable must first be tested for faults. Cable testing is therefore usually performed first in cable fault location. During the cable test, flash-overs are generated at the weak points in the cable, which can then be localised.

Locating the cable fault

Fault location technique on-site
Cable test van in China, 1975

The measures necessary for determining fault locations can be subdivided into individual steps.

Fault classification

Insulation and resistance measurement provides information on the fault characteristics. An insulation test measures the insulation resistance between conductor and screen; from the periodic measurement of resistance you can derive the absorption properties of the insulating material.

Pre-location

Pre-location is used to determine the fault distance. There are predominantly two methods for this.

Pulse reflection method

A pulse induced at the starting end of the cable reaches the cable fault with a speed of v/2 and is there reflected back toward the starting end of the cable. The elapsed time multiplied by the diffusion speed v/2 gives the distance to the source of the fault. See also: Time-domain reflectometer.

Transient method

In the transient method, a breakdown is triggered at the cable fault. This effects a low-resistance short circuit for a few milliseconds. This in turn produces two travelling waves diffusing in opposite directions. These waves are reflected at the cable ends so that they then travel toward each other again in the direction of the cable fault. The waves are unable to pass the fault because of the arc produced by the short circuit, so they are therefore reflected back again as with the pulse reflection method, which due to the burning short circuit results in a reversal of polarity. There are various ways to decouple and analyse these transients.

Route tracing and pinpointing

Route tracing is used to determine where the faulty cable lies and pinpointing is the process of determining the exact position of the cable fault.

Cable identification

In cable identification, the faulty cables are identified from the fault-free cables at the already determined site.

Fault conversion

After the cable fault is identified and located, it is then possible to “burn it in” using burner devices, in other words to convert it from a low-resistive to a high-impedance fault.

Cable test van

The conventionally used aid in cable fault testing and location is the cable test van. The van is installed with conventional cable measuring systems for quickly reaching the location of any cable fault. In 20 years that followed, over 2000 fault location vehicles were manufactured, more than half of which were intended for the former USSR. These methods of cable fault location quickly became established in Western Europe as well.