Flexible AC transmission system

A flexible alternating current transmission system (FACTS) is a system composed of static equipment used for the AC transmission of electrical energy. It is meant to enhance controllability and increase power transfer capability of the network. It is generally a power electronics-based system.

FACTS is defined by the IEEE as "a power electronic based system and other static equipment that provide control of one or more AC transmission system parameters to enhance controllability and increase power transfer capability."[1]

According to Siemens "FACTS Increase the reliability of AC grids and reduce power delivery costs. They improve transmission quality and efficiency of power transmission by supplying inductive or reactive power to the grid.[2]

Technology

Transmission on a no-loss line.
Series compensation.
Shunt compensation.

Series compensation

In series compensation, the FACTS is connected in series with the power system. It works as a controllable voltage source. Series inductance exists in all AC transmission lines. In long lines, when a large current flows, this causes a large voltage drop. To compensate, series capacitors are connected, decreasing the effect of the inductance. Also by connecting series capacitors in series with line, the inductive reactance between the receiving end and the sending end will be reduced due to which power factor of the system can be improved. But the effect on power factor is very little when compared to shunt capacitor.

Shunt compensation

In shunt compensation, power system is connected in shunt (parallel) with the FACTS. It works as a controllable current source. Shunt compensation is of two types:

Shunt capacitive compensation
This method is used to improve the power factor. Whenever an inductive load is connected to the transmission line, power factor lags because of lagging load current. To compensate, a shunt capacitor is connected which draws current leading the source voltage. The net result is improvement in power factor.
Shunt inductive compensation
This method is used either when charging the transmission line, or, when there is very low load at the receiving end. Due to very low, or no load – very low current flows through the transmission line. Shunt capacitance in the transmission line causes voltage amplification (Ferranti effect). The receiving end voltage may become double the sending end voltage (generally in case of very long transmission lines). To compensate, shunt inductors are connected across the transmission line. The power transfer capability is thereby increased depending upon the power equation


P=\left(\frac{EV}{X}\right)\sin(\delta)

\delta = power angle

Theory

In the case of a no-loss line, voltage magnitude at the receiving end is the same as voltage magnitude at the sending end: Vs = Vr=V. Transmission results in a phase lag  \delta that depends on line reactance X.

\begin{align}
\underline{V_s}&=V \cos\left(\frac{\delta}{2}\right) +jV \sin\left(\frac{\delta}{2}\right)\\
\underline{V_r}&=V \cos\left(\frac{\delta}{2}\right)-jV \sin\left(\frac{\delta}{2}\right)\\
\underline{I}&=\frac{\underline{V_s}-\underline{V_r}}{jX}=\frac{2V\sin{\left(\frac{\delta}{2}\right)}}{X}
\end{align}

As it is a no-loss line, active power P is the same at any point of the line:

P_s=P_r=P=V \cos\left(\frac{\delta}{2}\right) \cdot \frac{2V\sin{\left(\frac{\delta}{2}\right)}}{X}=\frac{V^2}{X}\sin(\delta)

Reactive power at sending end is the opposite of reactive power at receiving end:

Q_s=-Q_r=Q=V\sin\left(\frac{\delta}{2}\right) \cdot \frac{2V\sin\left(\frac{\delta}{2}\right)}{X}=\frac{V^2}{X}(1-\cos \delta)

As \delta is very small, active power mainly depends on  \delta whereas reactive power mainly depends on voltage magnitude.

Series compensation

FACTS for series compensation modify line impedance: X is decreased so as to increase the transmittable active power. However, more reactive power must be provided.
\begin{align}
P&=\frac{V^2}{X-Xc}\sin(\delta)\\
Q&=\frac{V^2}{X-Xc}(1-\cos \delta)
\end{align}

Shunt compensation

Reactive current is injected into the line to maintain voltage magnitude. Transmittable active power is increased but more reactive power is to be provided.
\begin{align}
P&=\frac{2V^2}{X}\sin\left(\frac{\delta}{2}\right)\\
Q&=\frac{4V^2}{X}\left[1-\cos\left(\frac{\delta}{2}\right)\right]
\end{align}

Examples of series compensation

Examples of FACTS for series compensation (schematic)

Examples of shunt compensation

Examples of FACTS for shunt compensation (schematic)

See also

References

In-line references
  1. Proposed terms and definitions for flexible AC transmission system(FACTS), IEEE Transactions on Power Delivery, Volume 12, Issue 4, October 1997, pp. 1848–1853. doi: 10.1109/61.634216
  2. Flexible AC Transmission Systems (FACTS) - Siemens
General references
  • Narain G. Hingorani, Laszlo Gyugyi Understanding FACTS: Concepts and Technology of Flexible AC Transmission Systems, Wiley-IEEE Press, December 1999. ISBN 978-0-7803-3455-7
  • Xiao-Ping Zhang, Christian Rehtanz, Bikash Pal, Flexible AC Transmission Systems: Modelling and Control, Springer, March 2006. ISBN 978-3-540-30606-1. http://link.springer.com/book/10.1007%2F3-540-30607-2
  • Xiao-Ping Zhang, Christian Rehtanz, Bikash Pal, Flexible AC Transmission Systems: Modelling and Control, 2nd Edition, Springer, Feb 2012, ISBN 978-3-642-28240-9 (Print) 978-3-642-28241-6 (Online), http://link.springer.com/book/10.1007%2F978-3-642-28241-6
  • A. Edris, R. Adapa, M.H. Baker, L. Bohmann, K. Clark, K. Habashi, L. Gyugyi, J. Lemay, A. Mehraban, A.K. Myers, J. Reeve, F. Sener, D.R. Torgerson, R.R. Wood, Proposed Terms and Definitions for Flexible AC Transmission System (FACTS), IEEE Transactions on Power Delivery, Vol. 12, No. 4, October 1997. doi: 10.1109/61.634216 http://ieeexplore.ieee.org/stamp/stamp.jsp?arnumber=00634216
This article is issued from Wikipedia - version of the Wednesday, March 02, 2016. The text is available under the Creative Commons Attribution/Share Alike but additional terms may apply for the media files.