Fluorescent-lamp formats
Since their introduction as a commercial product in 1939, many different types of fluorescent lamp have been introduced. Systematic nomenclature identifies mass-market lamps as to overall shape, power rating, length, color, and other electrical and illuminating characteristics.
Tube designations
Lamps are typically identified by a code such as FxxTy, where F is for fluorescent, the first number (xx) indicates either the power in watts or length in inches, the T indicates that the shape of the bulb is tubular, and the last number (y) is the diameter in eighths of an inch . Typical diameters are T12 or T38 (1 1⁄2 in or 38.1 mm) for residential lamps with magnetic ballasts, T8 or T26 (1 in) for commercial energy-saving lamps with electronic ballasts, and T5 or T16 (5⁄8 in) for very small lamps, which may even operate from a battery-powered device.
Designation | Tube diameter | Extra | |||
---|---|---|---|---|---|
(in) | (mm) | Socket | Notes | ||
T2 | 1⁄4 approx. | 7 | WP4.5x8.5d | Osram's Fluorescent Miniature (FM) tubes only
Sylvania Luxline Slim T2 Linear | |
T4 | 1⁄2 | 12.7 | G5 bipin | Slim lamps. Power ratings and lengths not standardized (and not the same) between different manufacturers | |
T5 | T16 | 5⁄8 | 15.9 | G5 bipin | Original 4–13 W range from 1950s or earlier.[1] Two newer ranges high efficiency (HE) 14–35 W, and high output (HO) 24–80 W introduced in the 1990s[2] |
T8 | T26 | 1 | 25.4 | G13 bipin/single pin/recessed double contact | From the 1930s,[3] more common since the 1980s.[4] |
T9 | T29 | 1 1⁄8 | 28.6 | G10q quadpin contact | Circular (circline) fluorescent tubes only |
T10 | 1 1⁄4 | 31.75 | G13 bipin | ||
T12 | T38 | 1 1⁄2 | 38.1 | G13 bipin/single pin/recessed double contact | Also from the 1930s, not as efficient as new lamps.[5] |
T17 | 2 1⁄8 | 54 | Mogul bipin | Large size for F90T17 (preheat) and F40T17/IS (instant start) | |
PG17 | 2 1⁄8 | 54 | Recessed double contact | General Electric's Power Groove tubes only |
Reflectors
Some lamps have an internal opaque reflector. Coverage of the reflector ranges from 120° to 310° of the lamp's circumference. Often, a lamp is marked as a reflector lamp by adding the letter "R" in the model code, so a F##T## lamp with a reflector would be coded as "FR##T##". Very high output (VHO) lamps with reflectors may be coded as VHOR. No such designation exists for the amount of reflector coverage the lamp has.
Reflector lamps are used when light is only desired to be emitted in a single direction, or when an application requires the maximum amount of light. For example, these lamps can be used in tanning beds or in backlighting electronic displays. An internal reflector is more efficient than standard external reflectors. Another example is color matched aperture lights (with about 30° of opening) used in the food industry for robotic quality control inspection of cooked goods.
Aperture lamps have a clear break in the phosphor coating, typically of 30°, to concentrate light in one direction and provide higher brightness in the beam than can be achieved by uniform phosphor coatings. Aperture lamps include reflectors over the non-aperture area. Aperture lamps were commonly used in photocopiers in the 1960s and 1970s where a bank of fixed tubes was arranged to light up the image to be copied, but are rarely found nowadays. Aperture lamps can produce a concentrated beam of light suitable for edge-lit signs.
Slimline lamps
Slimline lamps operate on an instant start ballast and are recognizable by their single-pin bases.
High output/very high output lamps
High-output lamps are brighter and are driven at a higher electric current, have different ends on the pins so they cannot be used in the wrong fixture, and are labeled F##T##HO, or F##T##VHO for very high output. Since about the early to mid-1950s to today, General Electric developed and improved the Power Groove lamp with the label F##PG17. These lamps are recognizable by their large diameter (21/8"), grooved tube shape and an R17d cap on each end.
Other tube shapes
U-shaped tubes are FB##T##, with the B meaning "bent". Most commonly, these have the same designations as linear tubes. Circular bulbs are FC##T#, with the outer diameter of the circle (not circumference or watts) in centimeters being the first number and the second number referring to the tube size.
Colors
Color is usually indicated by WW for warm white, EW for enhanced (neutral) white, CW for cool white (the most common), and DW for the bluish daylight white. BL is used for ultraviolet lamps commonly used in bug zappers. BLB is used for blacklight-blue lamps employing a woods glass envelope to filter out most visible light, commonly used in nightclubs. Other non-standard designations apply for plant lights or grow lights.
Philips and Osram use numeric color codes for the colors. On tri-phosphor and multi-phosphor tubes, the first digit indicates the color rendering index (CRI) of the lamp. If the first digit on a lamp says 8, then the CRI of that lamp will be approximately 85. The last two digits indicate the color temperature of the lamp in kelvins (K). For example, if the last two digits on a lamp say 41, that lamp's color temperature will be 4100 K, which is a common tri-phosphor cool white fluorescent lamp.
Halophosphate tubes | |||
---|---|---|---|
Numeric color code | Color | Approximate CRI | Color temperature (K) |
29 | Warm white | ~54 | 3000 |
35 | White | ~56 | 3500 |
33 | Daylight/Cool White | ~67 | 4300 |
25 | Natural/Universal White | ~75 | 4000 |
54 | Tropical Daylight | ~75 | 6500 |
Deluxe halophosphate tubes | |||
Numeric color code | Color | Approximate CRI | Color temperature (K) |
27 | Deluxe Extra Warm White | ~95 | 2700 |
32 | Deluxe Warm White | ~85 | 3000 |
34 | Deluxe White | ~85 | 3850 |
79 | Deluxe Natural | ~93 | 3600 |
38 | Deluxe Cool White/°Kolor-rite | ~92 | 4000 |
55 | Northlight/Colour Matching | ~94 | 6500 |
Tri-phosphor tubes | |||
Numeric color code | Color | Approximate CRI | Color temperature (K) |
827 | Warm white | ~85 | 2700 |
835 | White | ~85 | 3500 |
840 | Cool white | ~85 | 4000 |
850 | Sunlight | ~85 | 5000 |
865 | Cool daylight | ~85 | 6500 |
880 | Skywhite | ~85 | 8000 |
Multi-phosphor tubes | |||
Numeric color code | Color | Approximate CRI | Color temperature (K) |
927 | Warm white | ~95 | 2700 |
941 | Cool white | ~95 | 4100 |
950 | Sunlight | ~98 | 5000 |
965 | Cool daylight | ~95 | 6500 |
Special purpose tubes | |||
Numeric code | Fluorescent
lamp type |
Notes | |
05 | Germicidal lamps | No phosphors used at all,
using an envelope of fused quartz. | |
08 | Black-light lamps | ||
09 | Sun-tanning lamps |
Common tube ratings
This section lists the more common tube ratings for general lighting. Many more tube ratings exist, often country-specific. The Nominal Length may not exactly match any measured dimension of the tube. For some tube sizes, the nominal length (in feet) is the required spacing between centers of the lighting fixtures to create a continuous run, so the tubes are a little shorter than the nominal length.
Tube diameter in 1⁄8 in (3.175 mm) | Nominal length | Nominal power (W) |
---|---|---|
T5 | 6 in, 150 mm | 4 |
T5 | 9 in, 225 mm | 6 |
T5 | 12 in, 300 mm | 8 |
T5 | 21 in, 525 mm | 13 |
T8 | 18 in, 450 mm | 14 |
T8 | 2 ft, 600 mm | 18 |
T8 | 3 ft, 900 mm | 30 |
T8 | 4 ft, 1200 mm | 32 |
T8 | 5 ft, 1500 mm | 58 |
T12 | 18 in, 450 mm | 15 |
T12 | 2 ft, 600 mm | 20 |
T12 | 4 ft, 1200 mm | 40 |
T12 | 5 ft, 1500 mm | 65, 80 |
T12 | 6 ft, 1800 mm | 75, 85 |
T12 | 8 ft, 2400 mm | 125 |
European energy-saving tubes
In the 1970s, Thorn Lighting introduced an energy-saving 8 ft retrofit tube in Europe. Designed to run on the existing 125 W (240 V) series ballast but with a different gas fill and operating voltage, the tube operated at only 100 W. Increased efficiency meant that the tube produced only 9% lumen reduction for a 20% power reduction.[6] This first energy-saving tube design remains a T12 tube even today. However, follow-on retrofit replacements for all the other original T12 tubes were T8, which helped with creating the required electrical characteristics and saving on the then new (and more expensive) polyphosphor/triphosphor coatings, and these were even more efficient. Note that because these tubes were all designed as retrofit tubes to be fitted in T12 fittings running on series ballasts on 220–240 V supplies, they could not be used in 120 V mains countries with inherently different control gear designs.
Type | Diameter (in, mm) | Nominal length (ft, m) | Nominal power (W) | Notes |
---|---|---|---|---|
T8 | 1.0, 25 | 2, 0.6 | 18 | Retrofit replacement for 2 ft T12 20 W |
T8 | 1.0, 25 | 4, 1.2 | 36 | Retrofit replacement for 4 ft T12 40 W |
T8 | 1.0, 25 | 5, 1.5 | 58 | Retrofit replacement for 5 ft T12 65 W |
T8 | 1.0, 25 | 6, 1.8 | 70 | Retrofit replacement for 6 ft T12 75 W |
T12 | 1.5, 38 | 8, 2.4 | 100 | Retrofit replacement for 8 ft T12 125 W |
By around 1980 (in the UK, at least), most new fluorescent fittings were designed to take only the newer, retrofit tubes (the lamp holders are designed not to take T12 tubes, except for 8 ft length). The earlier T12 halophosphate tubes still remained available as spares until 2012 but only fit in older fittings and some modern fittings (they often fit in fittings employing twist lock lamp holders even though the fittings themselves, were not electrically designed for them).
US energy-saving tubes
In the 1990s, various energy-saving tubes were introduced in the US, but unlike the T8 tubes introduced in Europe, they are not retrofits and require new matching ballasts to drive them. Running a T8 tube with a ballast for T12 will reduce lamp life and can increase energy consumption.[7] The tube type should always match the markings on the light fixture.
Type | Diameter (in, mm) | Nominal length (ft) | Nominal power (W) | Notes |
---|---|---|---|---|
T12 | 1.5, 38 | 2 | 17 | |
T12 | 1.5, 38 | 4 | 34 | |
T12 | 1.5, 38 | 5 | 40 | |
T12 | 1.5, 38 | 8 | 59 | |
T8 | 1.0, 25 | 4 | 25 | Shoplite |
T5 tubes
In the 1990s, longer T5 tubes were designed in Europe (making it to North America in the 2000s), in addition to the shorter ones (mentioned above) already in use worldwide.
Tube diameter is 5⁄8 in (15.875 mm) | Length | Nominal power (W) | Notes | |
---|---|---|---|---|
High-efficiency | High output | |||
T5 | 563 mm (22.2 in) | 14 | 24 | Fits within a 0.6 m modular unit |
T5 | 863 mm (34.0 in) | 21 | 39 | Fits within a 0.9 m modular unit |
T5 | 1,163 mm (45.8 in) | 28 | 54 | Fits within a 1.2 m modular unit |
T5 | 1,463 mm (57.6 in) | 35 | 80, 49 | Fits within a 1.5 m modular unit |
T5 lamps are approximately 40% smaller than T8 lamps and almost 60% smaller than T12 lamps. T5 lamps have a G5 base (bi-pin with 5 mm spacing).[8]
See also
References
- ↑ Funke and Oranje, "Gas Discharge Lamps"; N.V Philips' Gloeilampenfabrieken (1951)
- ↑ "EC&M: The T5 Fluorescent Lamp: Coming on Strong". 2003-09-01. Retrieved 2008-09-28.
- ↑ "Covington, E. J. The Story Behind This Account of Fluorescent Lamp Development". Retrieved 2008-09-28.
- ↑ "Lawrence Berkeley National Laboratory: T-8 lamp retrofits". Retrieved 2008-09-28.
- ↑ "Lawrence Berkeley National Laboratory: History and problems of T12 fluorescent lamps". Retrieved 2008-09-28.
- ↑ Thorn Lighting Technical Handbook
- ↑ "Lighting Design Lab: http://www.lightingdesignlab.com/commercial/articles/Energy_Code.htm". 1995-11-01. Retrieved 2009-07-06. External link in
|title=
(help) - ↑ Lighting Research Center, "T5 Fluorescent Systems", , accessed 11-30-2009.
|